CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
1.6 General Design
The
CeilAiR
unit is housed in an aluminum frame type cabinet and is rated for indoor use. Access panels are located
on the front and rear of the cabinet for easy access to all components. Additional access may be obtained to some
components through the bottom of the unit on spot cooler configurations. The unit has an electrical box inside the
cabinet with a removable panel for accessing the electrical components. Operator controls may be conveniently
located on a wall within the space to be conditioned.
NOTE
Customer specified non standard features or design variations may not be described in this manual. Refer to
the installation and electrical drawings supplied with your unit for details on additional feature(s). In some
cases, an addendum to this manual may also be included to further describe the feature(s).
1-6
1.6.1 Electric Box Access
The electrical components are protected in an enclo-
sure located in the cabinet behind an access panel.
Before opening the access panel, turn off power at the
main power service disconnect switch. This removes
power from the system controller and shuts the unit
off.
1.6..2 Coil(s)
The cooling and optional hot water reheating coils are
aluminum finned/copper tube construction. The coils
are leak tested and cleaned before installation by the
factory.
1.6.3 Blower
The unit is equipped with a centrifugal blower with
forward curved blades. The blower is contained in a
double-width, double-inlet housing. The blower is
dynamically and statically balanced to minimize
vibration.
The blower motor is ODP industrial duty and utilizes
permanently lubricated ball bearings. Smaller
CeilAiR
units (models OHS-012/040) use direct drive blowers
(except “H”-series models configured for horizontal
discharge).
Larger units (models OHS-048/120) and horizontal
discharge units (models OHS-012/040-H), use a belt
driven blower. The belt driven blower motor is mounted
on an adjustable base for belt tensioning and is
furnished with an adjustable pitch sheave to adjust
blower speed (see Figure 13).
1.6.4 Temperature Sensor
As a standard for systems utilizing a wall mounted A-
Tech 1.1 or A-Tech 1.2 thermostat, the temperature
sensor is built into the thermostat for room air control.
The sensor monitors the room air conditions and
provides input signal(s) to the system controller. The
system controller manages the operation of the A/C
unit consistent with the setpoints entered.
As an option, the temperature sensor may be shipped
loose for field installation in the room to be condi-
tioned. Refer to the electrical drawing supplied with
your unit for details specific to your system.