CeilAir CW series Návod k obsluze Strana 35

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 60
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 34
(©July, 2008)
CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
4. Loosen the set screw in the side of the sheave
with an Allen wrench.
5. Remove the sheave key.
6. Adjust the blower speed by closing the sheave
one half turn to increase speed or opening the
sheave one half turn to decrease speed.
7. Replace the sheave key and tighten set screw.
8. Proper belt tension is achieved when the belt has
a deflection of ¾ inch per foot of span between the
blower and motor pulleys, with a firm pressure
placed on the side of the blower belt. Adjust the
blower belt tension by raising (to tighten) or
lowering (to loosen) the nuts on the adjustment
rods of the motor base.
CAUTION
If the belt tension is too tight, it will cause pre-
mature blower and/or motor bearing failure. If the
belt is too loose, the belt will slip and cause belt
squeals and eventual belt failure.
9. Restore power to system.
10. Check the current draw on the blower motor to
make sure it does not exceed the nameplate
rating of the motor.
11. If current draw exceeds nameplate rating of motor
repeat steps 1 through 9 to decrease blower
speed. If the motor pulls too much current, slow
the blower down by opening the adjustable sheave
one half turn at a time until the motor current is at
or below the nameplate FLA.
12. Check the motor overload on the blower starter to
confirm its setting is correct for the FLA of the motor.
2.9.6 Thermal Expansion Valve
All
CeilAiR
units utilizing thermal expansion valves
(TEV) control the flow of refrigerant entering the
evaporator to maintain a constant superheat of the
refrigerant vapor at the outlet of the evaporator. Super-
heat is the difference between the refrigerant vapor
temperature and its saturation temperature at that
pressure. By controlling superheat, the TEV keeps
nearly the entire evaporator surface active while not
permitting liquid refrigerant to return to the compressor.
The standard super-heat is factory set at 12-15°F and
should not need adjustment.
2.9.7 Hot Gas Reheat (Optional)
The hot gas reheat option incorporates a hot gas
reheat solenoid valve and a hot gas reheat coil. Under
normal operation when no reheat is required, the hot
gas reheat valve is de-energized and hot gas flows
directly from the compressor discharge to the con-
denser. When there is a call for reheat, the controller
energizes the hot gas reheat solenoid valve. The hot
gas reheat solenoid valve diverts hot gas to the reheat
coil, mounted directly downstream of the evaporator
coil, before it travels to the condenser. No adjustment
to the valve is necessary.
2.9.8 Hot Gas Bypass (Optional)
The two most common systems provided by SATS for
hot gas bypass are snap acting and full floating
described as follows.
2.9.8.1 Snap Acting Hot Gas Bypass
The snap acting hot gas bypass system provides for
some modulated capacity control and freeze protec-
tion. The hot gas bypass system includes a discharge
bypass valve that allows some hot gas from the
compressor discharge line to pass into the evaporator
coil to maintain a preset suction pressure. The
compressor cycles on demand from the controller.
The snap acting hot gas bypass system also provides
freeze protection for the evaporator coil by limiting the
minimum refrigerant pressure, preventing the surface
temperature of the evaporator coil from dropping below
32°F.
2-24
Figure 13- Belt Drive Blower
Zobrazit stránku 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 59 60

Komentáře k této Příručce

Žádné komentáře