CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-10
2.7 Utility Connections
2.7.1 Main Power
The
CeilAiR
product offering is available in single or
three phase variations and a wide range of voltages. It
is imperative that the unit nameplate be examined to
determine the operating voltage, frequency and phase
of the system (see Figure 5). The nameplate also
provides the full load amps (FLA), the current the unit
will draw under full design load, the minimum circuit
ampacity (MCA) for wire sizing, and the maximum
fuse size (MAX FUSE) for circuit protection. The unit’s
nameplate is located on the outside of the cabinet
within close proximity of the electrical box.
NOTE
If the nameplate states MAX FUSE/CKT BKR,
it is required to use fuses or a HACR type cir-
cuit breaker to protect the system. Other pro-
tection devices are not allowed based upon the
product listing.
The unit is provided with terminals for all required field-
wiring. It is important to identify the options that were
purchased with the unit in order to confirm which field
connections are required. Refer to the electrical
drawing(s) supplied with the unit for the power and
control field-wiring.
WARNING
Verify power is turned off before making connec-
tions to the equipment.
NOTE
All wiring must conform to local and national elec-
trical code requirements. Use of copper conduc-
tors only is required. Wiring terminations may
become loose during transit of the equipment;
therefore, it is required to verify that all wiring
terminations are secure.
It is important to verify that the main power supply
coincides with the voltage, phase and frequency
information specified on the system nameplate. The
supply voltage measured at the unit must be within
±10% of the voltage specified on the system name-
plate.
A manual fused disconnect switch must be installed
per local and national electrical codes for service of
equipment. Do not mount a shipped loose non-fused
service switch or customer supplied disconnect switch
Figure 5- Sample Nameplate