CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-9
2.6.3 Condensate Drain Line
2.6.3.1 Gravity Drain
A 7/8 inch OD copper (sweat type) line is provided to
drain the condensate drain pan. This line also drains
the humidifier, if applicable. The drain line must be
located so it will not be exposed to freezing tempera-
tures. The drain line should be the full size of the
connection. See the installation drawing provided with
your unit for the size and location of the condensate
drain line.
NOTE
During normal operation the optional humidifier
drains (hot) water into the condensate drain
line. As an option, a separate drain line may be
provided for the humidifier.
2.6.3.2 Condensate Pump (See Figure 4)
A condensate pump is used for automatic removal of
condensate from the air conditioner and flush water
from the humidifier (if applicable). A p-trap must be
installed for proper condensate drainage. The height of
the trap must be a minimum of 2 inches on most
standard systems to ensure proper water drainage of
the drain pan. The condensate pump discharge line
should be 1/2 inch OD maximum copper or vinyl tubing
to prevent excessive back flow to unit.
NOTE
Pour some water into the condensate drain(s)
prior to start-up. This fills the trap and prevents
air from being drawn up the drain lines.
2.6.4 Humidifier (Optional)
CeilAiR
systems utilize an electrode steam humidifier.
The humidifier empties into the condensate drain line
during the flush/drain cycle. A water supply line must
be connected to the copper tubing connection supplied
by the factory. Refer to the installation drawing pro-
vided with your unit for the size and location of the
connection. The humidifier requires normal tap water
as the water supply. If the supply water is high in
particulate, an external filter may be needed.
CAUTION
Do not use demineralized water.
Refer to the humidifier operator’s manual, supplied with
the equipment, for complete manufacturer’s informa-
tion on the humidifier and the supply water recommen-
dations.